http://irepo.futminna.edu.ng:8080/jspui/handle/123456789/31308| Title: | Analysis of Magnetic Field Exposure at Extremely Low Frequency (ELF) in 330kV Transmission Switchyards |
| Authors: | Ocheni, A. U. U Oyedum, O. D. Ndubuka, N. M. Moses, A. S |
| Keywords: | ELF magnetic field, Switchyards, Transmission stations, ANOVA, Electro pollution, and Occupational exposure |
| Issue Date: | 12-Jun-2023 |
| Publisher: | Journal of Materials Engineering, Structures and Computation |
| Citation: | A. U. U. Ocheni, O. D. Oyedum, N. M. Ndubuka, A. S. Moses (2023). Analysis of Magnetic Field Exposure at Extremely Low Frequency (ELF) in 330kV Transmission Switchyards. Journal of Materials Engineering, Structures and Computation 2(2) pp.12-19. https://doi.org/10.5281/zenodo.8027569 |
| Abstract: | The present study assessed the exposure levels of extremely low frequency (ELF) magnetic fields in five 330 kV transmission switchyard of generation stations located in north-central, Nigeria. In conformity with IEEE standards of measurement procedures, ELF magnetic field levels were detected in the switchyards using Extech 480826 triple-axis EMF metre via spot technique at three different observation heights of 1.0, 1.5 and 1.8 m. The data obtained were subjected to analysis using the One-way ANOVA SPSS package. The results demonstrated occupational significant differences of (p < .001) between 330 kV switchyards of Shiroro Hydro-plant and Geregu Phase II Gas-plant, significant differences of (p = .045) between switchyards of Geregu Phase I Gas-plant and Geregu Phase II Gas-plant, and also significant differences of (p < .001) in occupational exposure was demonstrated between switchyards of Jebba Hydro-plant, Kainji Hydro-plant when separately compared to Geregu Phase I and Geregu Phase II Gasplants. However, non-significant differences occurred between switchyards of Shiroro Hydro-plant and Jebba Hydro-plant, Kainji Hydro-plant and Geregu Phase I Gas-plant, and Jebba Hydro-plant with Kainji Hydro-plant. This study has revealed the occurrence of field pollution within the switchyard and the variation of ELF magnetic field magnitude from between switchyards |
| URI: | http://irepo.futminna.edu.ng:8080/jspui/handle/123456789/31308 |
| Appears in Collections: | Physics |
Files in This Item:
| File | Description | Size | Format | |
|---|---|---|---|---|
| Analysis of Magnetic Field Exposure at Extremely.pdf | 351.23 kB | Adobe PDF | View/Open |